Outside Air Processing Unit (FXMQ_MFVJU)
Outside Air Processing Unit (FXMQ_MFVJU)
Both fresh air treatment and heating and cooling can be achieved successfully in a single system via heat pump technology without the usual design problems associated with balancing air supply and discharge. Fan coil units and outdoor air processing unit can be connected to the same refrigerant line, resulting in enhanced design flexibility and a significant reduction in total system costs.
- Can be connected to all North American Daikin VRV systems
- Available in three capacities, nominal 48, 72 and 96 MBH
- The nominal airflow are 635, 988, and 1,236 CFM respectively
- External static pressure capabilities of up to 1.03" W.G. allows for flexibility with duct work and filtration choices
- The indoor unit is controlled to a set cooling and heating discharge air temperature allowing the flexibility to integrate with a standard Daikin indoor unit or duct directly to the space
- A low profile design of only 18.5" high reduces the required installation space and can eliminate mechanical rooms or additional structural supports associated with traditional outside air systems
- Indoor Air Quality options include MERV 8 and 13 filters and filter boxes
- Connects directly and seamlessly into the Daikin local and centralized control suite
Operational Characteristics
When the suction air temperature is between 66°F and 109°F the Outside Air Processing Unit operates in cooling, and when between 23°F and 59°F, it operates in heating. The OA processing unit will work in energy saving fan only between 59°F and 66°F; this is not configurable.